ZONE CONTROL SYSTEMINSTALLATION AND OPERATION MANUAL
4.2 THERMOSTAT INSTALLATION: DSL-520PLOCATIONThe most important consideration in installing your DSL-520P Communicating Zone thermostatis where to loc
8 SlimZone PremierFigure 4.2: SZP Wiring Diagram
SlimZone Premier 9EMERGENCY
10 SlimZone Premier4.4 WIRING INFORMATIONUse #18AWG (nonshielded) copper wire for all system wiring; thermostats may use 18-24AWGwire. Thermostats an
4.6 SLIMZONE ENVIRONMENTAL MODULE (SZEM)INTRODUCTIONThe SlimZone Environmental module (SZEM) is anoptional component in the SlimZone Premier system.
12 SlimZone Premier5. SYSTEM OPTIONS AND OPERATION5.1 INTERACTION BETWEEN MODULESThe SZP control module is the central processing unit in the SlimZone
The DSL-520P thermostat provides the following information to the SZP control module:• heating, cooling, and fan requirements•room temperature• temper
14 SlimZone PremierMINIMUM EQUIPMENT ON TIME (short cycle protection)The minimum amount of time the thermostat will call for heating or cooling may be
override is still allowed but for a duration of one (1) hour (unoccupied mode). The system willremain in the TEMPORARILY SUSPENDED mode until the pro
16 SlimZone PremierSMART FAN ENABLEWhen Smart Fan is enabled and constant fan is selected at the control module (global constantfan), the fan will rem
SlimZone Premier iTABLE OF CONTENTS1. INTRODUCTION...
5.6 SEQUENCE OF OPERATION5.6.1 TIMESHARE MODENote: The following assumes the control module is in the auto mode of operation.A. Control module receive
18 SlimZone Premier• If the control module receives a high limit (in heating) or low limit (in cooling) alarm from theSZEM module, it will downstage t
5.8 FLOW DIAGRAMLEGEND... Screen... Lists options selected by pressing the indicated button #... Actions which occur behind the s
Are you sure? Yes No12:00AFriJan01/99Auto ModeFan AutoSchedule:NormalOptionsSchedule:SuspendedProgramming12:00A FriJan01/99System OffCool Mode
42System Type:HeatpumpHeat pumpHeat/CoolMay select:Only appears whenHeat pump is selectedAppears for each #of stage selected.Only appears whenHeat pum
22 SlimZone Premier6. START UP AND TESTSETUPA. Check that the SZEM Environmental module and its components are properly installed.B. Check all zone th
D. Go to the Equipment Test screen (Figure 5.2). Following the menus, turn each equipmentoutput relay ON and OFF to check that on-board relays are fu
24 SlimZone PremierL. Heating cycle: •Place the system in the heat mode.•Bring the heating setpoint of the Must-Service zone to its highest setting.•
N. Go to the Bypass Setup screen and initiate the setup sequence. Note that this processmay take up to approximately 5 minutes and you cannot abort t
TROUBLESHOOTING GUIDEPROBLEM POSSIBLE CAUSE SOLUTIONNo heat/cooling in Zone thermostat(s) Select heat, cool or auto mode house of operation at therm
ii SlimZone Premier6. START UP AND TEST...
GLOSSARYAuxiliary/Emergency Applicable to heat pump systems only. Auxiliary heat refers to the 3rd heat Heat stage (W3). In the event of a heat pump c
28 SlimZone PremierAPPENDIX A: List of FiguresFIGURE 3.1: TYPICAL SYSTEM DIAGRAM...
Zone ScheduleSlimZone Premier 29
SLIMZONE PREMIER-SZP-ZONE DIAGRAM30 SlimZone Premier
WARRANTYLimited One Year WarrantyRobertshaw warrants to the original purchaser that its product and component parts will be free fromdefects in workma
SlimZone Premier 110-908CUni-Line North America Canadian DivisionP.O. Box 2000 5785 Kennedy RoadCorona, CA 92879-1736 Mississauga, Ontario L4Z 2G3Unit
SlimZone Premier 11. INTRODUCTIONThe SlimZone Premier (SZP) is a commercial/residential HVAC (Heating/Ventilation/AirConditioning) zone control system
2 SlimZone Premier• Minimum on/off times (short cycle protection)• Occupied/unoccupied cycle capability • Manual or automatic changeover • Smoke detec
R. All zones served by a SlimZone control module should have the same basic load characteristics(i.e., do not put 4 zones on an east exposure, and the
4 SlimZone Premier3.3 ENVIRONMENTAL MODULEITEM QUANTITY CONSIDERATIONSSZEM environmental module one (1) contains two (2) remote temperatureprobes, and
Figure 3.1: Typical System DiagramSlimZone Premier 5AND ACCESSORIES.OPTIONAL ACCESSORIES.
6 SlimZone Premier4. SYSTEM INSTALLATION4.1 SLIMZONE PREMIER CONTROL MODULE (SZP)4.1.1 REMOVAL AND INSTALLATION OF THE DOORInstaller should touch a gr