SlimZone DeluxeSlimZone DeluxeZONE CONTROL SYSTEMINSTALLATION AND OPERATIONMANUAL
IMPORTANT:In order to avoid electrical interference to sensitive components, no wiring to the panelshould cross over the panel.6.6 LOGIC PANEL POWER
Bypass dampers should be installed in the main supply plenum upstream from turningvanes, transitions, and zone dampers. Bypass air may be directed thr
7.2 REVERSING VALVE OPERATIONThe O/B terminal can be configured as O or B. The factory O/B default is set to cooling (O).Reversing valve output does
7.8 ZONE UPSTAGINGUpstaging can be based on a selected number of zones calling instead of time. Upstaging tosecond and third stages may be set to 2 z
7.14 AUXILIARY HEAT (HEAT PUMP SYSTEMS)Before auxiliary heat is energized, a 5-minute (factory default) time limit is initiated on a callfor heating.
SlimZone Deluxe112701-002Logic Panel2701-003ExpanderModule6.9 inches17.5 cm3.7 inches9.4 cm7.4 inches18.8 cm2.0 inches5.1 cm9. LOGIC PANEL BACKPLATE
SlimZone Deluxe12HVAC SYSTEMDischargeAir LimitControlBypass DamperZoneDampersFrom HVAC panelto Logic panelLogic Panel andZone DamperTransformersZoneTh
SlimZone Deluxe1324V24NGNDPC24NPO24L24NGYWRPC24NPO24L24NGYWRPC24NPO24L24NGYWRSWCOMHEATCOOLOFFEHFANSCCSMKCLKBPCLBPHBPLIMCLLIMHLIMRHW1RO/BW2/O/BY1RCY2RG
SlimZone Deluxe14POWERSEEDETAILAZONE 1SEEDETAILBZONE 2SEEDETAILBZONE 3SEEDETAILBMODESEEDETAILCINPUTSEEDETAILDEQUIPMENTSEEDETAILEFANSEEDETAILF24V24NGND
SlimZone Deluxe15Robertshaw SlimZone DeluxeMaster Logic PanelPOWERDETAIL A24V24NGND24VAC, 40VATRANSFORMERFUSETO PRIMARYVOLTAGETO COMMONGROUND1/4”NOTE:
SlimZone Deluxe16Robertshaw SlimZone DeluxeMaster Logic PanelZONEDetail B1/4”NOTE: Use standard nonshielded 18-24 AWG copper wire for all terminal la
SlimZone Deluxe17Robertshaw SlimZone DeluxeMaster Logic PanelMODEDetail C1/4”NOTE: Use standard nonshielded 18-24 AWG copper wire for all terminal la
SlimZone Deluxe18Robertshaw SlimZone DeluxeMaster Logic PanelINPUTDetail D1/4”NOTE: Use standard nonshielded 18-24 AWG copper wire for all terminal l
SlimZone Deluxe19Robertshaw SlimZone DeluxeMaster Logic PanelEQUIPMENTDetail EandFANDetail F1/4”NOTE: Use standard nonshielded 18-24 AWG copper wire
SlimZone Deluxe20SW7SW5SW4SW6SW3SW2SW1RobertshawSlimZone DeluxeSwitch LocationsandUser Settings1 2 3SWITCH NUMBER SWITCH POSITION OPERATIONSW
SlimZone Deluxe21SW7SW5SW4SW6SW3SW2SW1RobertshawSlimZone DeluxeSwitch LocationsandControl SettingsforConventionalHeat/Cool SystemsorHeat Pumps54321ON/
SlimZone Deluxe22SW7SW5SW4SW6SW3SW2SW1RobertshawSlimZone DeluxeSwitch LocationsandControl SettingsforUpstage DelayUpstage ZonesUpstage Auxiliary Heat5
SlimZone Deluxe23SW7SW5SW4SW6SW3SW2SW1RobertshawSlimZone DeluxeSwitch LocationsandControl SettingsforG2 Fan Output54321ON/OFF SWITCH
SlimZone Deluxe24SW7SW5SW4SW6SW3SW2SW1RobertshawSlimZone DeluxeSwitch LocationsandControl SettingsforG2 ECONOMIZERandTime Delay Override54321ON/OFF S
SlimZone Deluxe2523. CONTROL SETUP — INSIDE DOOR LABEL
TABLE OF CONTENTS1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12. OPERAT
SlimZone Deluxe26POWER24VLive connection fromthe 24VAC trans-former to power thepanel.24NNeutral or commonconnection from the24VAC transformer.GNDTo
25. TEST, CHECK, AND STARTUP PROCEDURES1. After all wiring has been landed to the logic panel, disconnect the RH/RC wire fromthe panel to the equipme
26. TROUBLESHOOTING GUIDE27. LOGIC PANEL SPECIFICATIONSPanel Power Requirements Dedicated 24 VAC, 24VA TransformerMinimum Power Consumption 250mA (Mas
Ambient Temperature Maximum Current-4˚F (-20˚C) 3.40 amps32˚F (0˚C) 2.98 amps68˚F (20˚C) 2.50 amps104˚F (40˚C) 2.03 amps122˚F (50˚C) 1.80 amps140˚F (6
SlimZone Deluxe30NOTES:
SlimZone Deluxe31NOTES:
SlimZone Deluxe 110-981CUni-Line North America Canadian DivisionP.O. Box 2000 5785 Kennedy RoadCorona, CA 92879-1736 Mississauga, Ontario L4Z 2G3Unite
TABLE OF CONTENTS (CONTINUED)18. BYPASS SIZING CHART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1019.
1. INTRODUCTIONThe Robertshaw Slimzone Deluxe logic panel is designed for residential and light commercialconstant volume heating and air conditionin
3. SAFETY INSTRUCTIONS• Leave all primary power disconnected until installation is complete.• Sharp metal edges may cause damage to wires. Use care d
•Proper location of motorized zone dampers is important. Motorized zone dampersshould be located on the trunk lines as close to the main supply plenum
5.2 EXPANDED SYSTEM REQUIREMENTS*Use with resistor kit5.3 OPTIONAL ITEMS FOR BOTH BASIC AND EXPANDED SYSTEMSlimZone Deluxe4ITEM QUANTITY DESCRIPTION
6. SYSTEM INSTALLATION6.1 UNPACKING THE 2701-002 LOGIC PANELRemove the 2701-002 from the shipping carton and protective bubble pack. Touch agrounded