Terminal Function
One Stage Models RS4110, RS5110 and RS6110
TERMINAL
EQUIPMENT TO
CONNECT
DESCRIPTION
C
24V AC
Common Connection
For input of 24V AC common side of transformer.
Connect to provide always-on backlight/nightlight.
RH/R
24V AC
Hot Connection
For input of 24V AC hot side of transformer.
RC
24V AC
Hot Connection
When cooling transformer is used for input of 24V
AC hot side of transformer.
Jumper from RH to RC must be removed.
Y1*
First stage
compressor
connection
Energizes on a call for first stage of cooling.
Energizes on a call for first stage of heating when
configured as a HP.
W1*
First stage
heat connection
Energizes on a call for first stage of heating when
configured as a Non-HP.
G
Indoor fan
connection
Energizes with Y1 and Y2.
Energizes with W1 and W2 if the Gas/Elec switch is
set to electric.
Energizes when fan is switched to ON.
O Energizes for heat pump cool reversing valve.
B Energizes for heat pump heat reversing valve.
* This thermostat can be used as a heat-only or cool-only thermostat. Therefore, it is not
always necessary to use both W1 and Y1.
Two Stage Models RS4220, RS5220 and RS6220
TERMINAL
EQUIPMENT TO
CONNECT
DESCRIPTION
L
24V AC
Compressor Fault
Output
For input of fault signal from a compressor.
Y2
Second stage
cooling
connection.
Energizes on a call for second stage cooling (aux.).
W2
Second stage
heat connection
Energizes on a call for second stage heating (aux.).
E
Emergency Heat
Connection
Energizes on a call for emergency heat.